A PSC motor will not start with an open winding. It may hum until the internal overload trips.
- Disconnect the power to the unit
- Discharge the capacitors
- Disconnect the wires from the compressor terminals
- Set your multimeter to low ohms
- If you detect no Ohms reading from the start to common or reading from the run to common,you have an open overload or winding.
- Check the resistance between the run and start terminal. If there is resistance, the overload is open
- If there is no resistance, you have an open winding.