How To Diognose and Open Compressor Winding, Single Phase

A PSC motor will not start with an open winding.  It may hum until the internal overload trips.

  • Disconnect the power to the unit
  • Discharge the capacitors
  • Disconnect the wires from the compressor terminals
  • Set your multimeter to low ohms
  • If you detect no Ohms reading from the start to common or reading from the run to common,you have an open overload or winding.
  • Check the resistance between the run and start terminal.  If there is resistance, the overload is open
  • If there is no resistance, you have an open winding.

How to Diognose Non-Condensables

Air, nitrogen, hydrogen and other foreign gasses present in a refrigerant system are referred to as non-condensables since they will not condense into a liquid at pressures encountered in a refrigeration system. These gases will accumulate in the condenser coil and take up valuable condenser coil circuiting.

Causes

  • Poor installation skills
  • Failure to properly evacuate the system after the system has been opened

Symptoms

Systems running with non-condensables present will experience higher than required head pressure.  The suction pressure will be low if there is no subcooling present  If subcooling is present, the suction pressure may be slightly high with fixed metering systems and may be normal with TXV systems.

The subcooling level with non-condensables will be lower than required.  If no subcooling is present, there will be flash gas in the liquid line before the metering device.

The superheat level will be high when flash gas is present.  If there is subcooled liquid entering the metering device and the suction pressure is high with a fixed metering system, the superheat may be low.  If the system is using a TXV, the superheat may be normal.

Test the System

  • The system must have a discharge line pressure port to perform this test.
  • Pump the refrigerant into the condenser coil by running the compressor with the liquid service valve closed.  Only pump the system down to 0 PSIG suction pressure.  Never run in a vacuum.
  • Shut off the condensing unit when pump-down is finished.  Disconnect power to the compressor and then call for cooling so that only the condenser fan runs.
  • Measure the temperature of the outdoor air and air leaving the condenser coil.  When they are equal to one another, shut off the condenser fan.
  • Compare the pressure in the condenser coil to the temperature of the outdoor air.  The pressure you read should equal the pressure at the saturation temperature equal to the outdoor air temperature.  If the pressure is higher than it should be, non-condensables are present.  If non-condensables are present, recover the refrigerant and recharge.

How to Diognose an Over-Feeding Metering Device

An evaporator coil that is receiving a higher than normal flow of refrigerant through the metering device will operate in a flooded condition.  The system may experience high humidity complaints, compressor starting problems, or compressor failure.

Causes

  • Piston too large in fixed metering device
  • Dirty piston seat not allowing metering device to seat properly
  • TXV sensing bulb not insulated or in good contact with the suction line

Symptoms

The metering device isolates the high side from the low side pressure.  When an overfeeding condition is present, the suction side of the system operates in a flooded state while the high side of the system operates in a starved state.  The suction pressure will be high and the superheat low.  The liquid pressure will be low and the subcooling will be low.

If the system is using a reciprocating type compressor, it may apear that the compressor valve plate is bad.

Procedure

  • Close the liquid service valve and pump the system down.  if the system does not hold a pump down and the liquid line service valve is properly closed.  Replace the compressor. (Recip)
  • If the system holds a pump down cycle, inspect the metering device to determine if it is seated properly or too large.
  • If the system has a TXV, make sure the sensing bulb is properly insulated and in good contact with the suction line.  If it is not, correct the problem.  If it is, replace the TXV.

How to Diognose Restricted Metering Device

Restrictions in the metering device will prevent the evaporator coil from receiving the proper amount of refrigerant.  The restriction will cause the suction pressure to be too low.  With low suction pressure present, the saturation temperature of the refrigerant in the evaporator is very low.  Because of low saturation temperature, freezing of the evaporator surface is likely.

Causes

  • Undersized fixed metering device
  • Failed expansion valve
  • Debris in metering device
  • Moisture freezing at metering device

Symptoms

Symptoms running with a metering restriction will have low suction pressure along with high superheat.  The liquid pressure will initially be low which will make the system appear undercharged.  When refrigerant is added to the system, the liquid pressure will rise but the suction pressure will remain low.  At this point you should be able to identify there is a problem in the liquid circuit.  If subcooling is measured, at this time, it will be high.  The high subcooling level is an indication that excess refrigerant is being stored in the condenser coil.

There will be no obvious sign of frosting between the consenser coil and the metering device.

Procedure

  • If the liquid and suction pressure are low, and no obvious sweating or frosting of the liquid line is present, add refrigerant.  If the system is undercharged, both pressures will begin to rise.  If the liquid pressure rises significantly, but the suction pressure remained low, the liquid circuit has a restriction.
  • Check the temperature of the liquid line at the outlet of the condenser coil and at the inlet to the metering device.  If you detect a large temperature drop, there is a pressure drop between the two test points.  Isolate the restriction and make the repair.
  • If there is no temperature drop between the outlet of the condenser and the inlet of the metering device, yet the liquid pressure is elevated, suction pressure is low, superheat and subcooling high, the problem is in the metering device.
  • Pump the system down or recover the refrigerant and inspect the metering device for proper size, operation or debris.  Replace if necessary

Diognosing Liquid Line Restrictions

Restrictions in the liquid line will prevent the evaporator coil from receiving the proper amount of refrigerant.  The restriction will cause a large pressure drop between the condenser and the metering device.  This large pressure drop can be detected by checking the temperature of the liquid line at the outlet of the condenser coil and at the inlet to the metering device.

Causes

  • Restricted liquid line dryer
  • Undersized liquid line
  • Excessive liquid line pipe fittings
  • Kinked liquid line.

Symptoms

Systems running with a liquid line restriction will have low suction pressure along with high superheat.  The liquid pressure will initially be low which will make the system appear undercharged.  When refrigerant is added to the system, the liquid pressure will rise but the suction pressure will remain low.  At this point, you should be able to identify there is a problem in the liquid circuit.  If subcooling is measures, at this time, it will be high.  The high subcooling level is an indication that excess refrigerant is being stored in the condenser coil.

Look for frosting or sweating of the liquid line or liquid line dryer.

Procedure

  • If the liquid and suction pressure are low, and no obvious sweating or frosting of the liquid line is present, begin to add refrigerant.
  • If the system is undercharged, both pressures will begin to rise.  If the liquid pressure rises significantly, but the suction pressure remains low, the liquid circuit has a restriction.
  • Check the temperature of the liquid line at the outlet of the condenser coil and at the inlet to the metering device.  No significant drop in temperature should be detected.  If you detect a large temperature drop, there is a pressure drop between the two test points.  Isolate the restriction to make the repair.
  • If there is no temperature drop between the outlet of the condenser and the inlet of the metering device, yet the liquid pressure is elevated, suction pressure is low, superheat and subcooling is high, perform diagnostics for a restricted metering device.

How to Diognose High Heat Load, Fixed Orface or TXV

High evaporator heat load occurs when there is excessive heat entering the refrigerant at the evaporator coil.  This condition can cause the compressor to shut off on it’s internal overload, or trip the electrical circuit breaker.

Causes

  • Infiltration of unconditioned air into the return duct
  • New systems started on a very hot day
  • Economizer/fresh air damper open on a hot day
  • Temporary high people loads
  • System undersized for heat gain

Symptoms

  • Systems running with high evaporator loading will run at pressures above factory required levels.  Abnormally high superheat and normal subcooling levels will be present when the evaporator coil is exposed to higher than allowed heat load.  The high heat load condition could cause the evaporator coil temperature to be very warm.  The compressor shell and hot gas temperature will be extremely high.

TXV  A system with a TXV may keep superheat level close to the required range of 10 to 15F.  In exteme cases of high load the superheat may go higher.

Procedures

  • Measure the temperature of the conditioned space and then check the temperature of the air entering the evaporator coil at the filter rack.  If the air entering the evaporator is warmer that the conditioned space, infiltration of unconditioned air is present.
  • If the system has an economizer or fresh air damper, make sure it is closed.
  • If the system is new and start up is on a hot day, allow time for the indoor temperature to fall within charging chart range.
  • If the system is still overloaded and the outdoor air temperature is within design range for your area, run a heat load to determine if the system is properly sized.

How to Identify Low Evaporator Heat Load, TXV

Low evaporator heat loading occurs when there is not enough heat entering the refrigerant at the evaporator coil.  This condition can cause the evaporator coil to form a coating of frost or ice on it’s surface.  In extreme cases, superheat could fall to zero degrees and liquid refrigerant can flood back to the compressor.

Causes:

  • Dirty return air filter
  • Dirty indoor fan blower
  • Indoor fan motor not on high speed
  • Undersized duct work
  • Dirty evaporator coil
  • Thermostat set-point too low

Symptoms

Systems running with low evaporator loading will run at pressures below factory required levels.  The TXV may hunt in an attempt to maintain proper superheat levels.

The low heat load condition could cause the evaporator coil temperature to be very cold.  Ice or frost may form on the evaporator surface and suction line surface.  The compressor shell may sweat and the hot gas temperature will be cool.

Repair Procedure

  • Thaw the evaporator coil if frost or ice has formed.
  • Inspect the return air filter and replace if dirty.
  • Inspect the evaporator coil and clean if dirty
  • Inspect the indoor blower and clean if dirty
  • Make sure the indoor blower motor is operating at high speed
  • Make sure the supply and return duct are sized properly
  • Measure indoor CFM for proper flow.  350 to 450 CFM per ton.

HVAC Marketing

HVAC Marketing is everything you do to promote your business.  Advertising is part of marketing.  This includes your business cards, letterhead and logo.  A big part of marketing for HVAC includes the moving billboards called your service vans. 

Marketing works both ways.  If you do great work, marketing will spread the word.  If your work is crap, marketing will spread the news like wildfire.  Before you start intensive marketing, make sure you deliver quality services.

Do all the basic “Guerrilla Marketing” techniques.  You will find these in the classic book by Jay Conrad Levinson.   Guerrilla Marketing, 4th edition: Easy and Inexpensive Strategies for Making Big Profits from Your Small Business   See the book review on this site.

Many HVAC contractors attempt to develop their brand through radio or TV.  I’m a firm believer that if you can’t directly measure the results of your marketing, the marketing needs to be free.  Things like delivering a great service, clean trucks and facilities are excluded.

Don’t throw your money away on marketing and advertising unless you are willing to meticulously track the results.

The best advertising for HVAC contractors is called direct response advertising.  This means you send a postcard or other tractable ad those results in a sale.  You know what you are going to spend and the results you expect.

We have found the only business model that is predictably successful is the Maintenance Department Business Model.  In this business model the contractor sells HVAC tune-ups, converts them to annual service agreements and the annual service agreements produce a predictable number of high profit HVAC Replacement sales.  See the “MANTENANCE DEPARTMENT MANIFESTO”.  The content in the “Maintenance Department Manefesto” is available on this blog and other HVAC marketing sites for free.  If you want this information in an organized step by step format, you will save many hours for just a few dollars.  Reguardless, make sure you sign up for updated and new content by subscribing to our mailing list.

Another book that we recommend is Ron Smith’s HVAC Spells Wealth
See the review on this site.  Ron’s book, it is one of the best resource available for the HVAC Service replacement business and belongs in every HVAC library.

HVAC Consultant

To: HVAC Contractors

We want your business to be successful and profitable.  If you are serious about growing your business, you can email or call us at any time 24/7 with any question, no charge, no kidding.  mg@iheatcool.com

Grow your HVAC business by using the time proven methods.  Don’t gamble on unproven or untested ideas.  Listen to the industries top HVAC Consultant or consultants.   Don’t take our word for it, do your research and verify our recommendations.

There is no get rich quick business model in residential/commercial HVAC.

The time proven growth model is to sell tune-ups and train your tune-up specialist to convert those single tune-ups to annual service agreements.  The HVAC system replacement sale “closing rate” for service agreement customers is almost three times the sales to non-agreement customers.

You might try a shortcut and market annual service agreements, but we tried every possible combination and selling service agreements just doesn’t work.  You must market tune-ups.

Of course you could pioneer a new marketing method and it might work, or you can follow the time proven GET RICH SLOW method.

You can read the blogs and articles of reputable experts at no cost or you can purchase the Maintenance Department Manifesto and get step-by-step instructions how and where to get started and quickly implement the maintenance department business model.

Please be aware, if you buy this eBook we get paid a commission.  You can get the information for free, if you want to put in the hours searching for the information.

You should also read Ron Smith’s book, “HVAC Spells Wealth”  (we receive no commission on this)

For great marketing materials subscribe to Matt Michel’s “Servive Roundtable” (we receive no commission on this)

Entry level HVAC Training, our HVAC Jobs board and Free EPA Certification Study Guide are at HVACjobsTraining.com

How To Diognose Low Evaporator Heat Load, Fixed Orifice

Low evaporator heat loading occurs when there is not enough heat entering the refrigerant at the evaporator coil.

This condition can cause the evaporator coil to form a coating of frost or ice on it’s surface.  In extreme cases, superheat could fall to 0 degrees and liquid can flood back to the compressor.

Symptoms

  • Fixed orifice.  Systems running with low evaporator loading will run at pressures below factory required levels.  Abnormally low superheat and subcooling levels will be present when the evaporator coil lacks heat load.  The low heat load condition could cause the evaporator coil temperature to be very cold.  Ice or frost may form on the evaporator surface and suction line surface.  The compressor shell may sweat and the hot gas temperature will be cool.

Procedure

  • Thaw out the evaporator coil if ice or frost are present.
  • Check airflow (350-450 CFM per ton)
  • Determine cause of low air flow, dirty filter, dirty evap coil, dirty blower, blower motor speed, restricted return duct.
  • Make sure thermostat setpoint is not too low.
  • Correct airflow problem.
  • Check for proper refrigerant charge.